©2025 Daikin Applied, Minneapolis, MN. All rights reserved throughout the world.This document contains the most current product information as of this printing. Daikin Applied Americas Inc. has the right to change the information, design, and construction of the product represented within the document without prior notice. For the most up-to-date product information, please go to www.DaikinApplied.com. ™® MicroTech, Rebel, Maverick II, Roofpak, Pathfinder, Trailblazer, Magnitude, Navigator, and Daikin Applied are trademarks or registered trademarks of Daikin Applied Americas Inc. The following are trademarks or registered trademarks of their respective companies: BACnet from American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc., and Windows from Microsoft Corporation.

መግቢያ

  • አጠቃላይ መረጃ
  • ይህ ማኑዋል በማይክሮቴክ አፕሊድ ጣራዎች እና እንዲሁም ከዳይኪን አፕሊይድ አየር እና ውሃ-ቀዝቃዛ ቻይለር አሃድ ተቆጣጣሪዎች ጋር ለመጠቀም የርቀት የተጠቃሚ በይነገጽ እንዴት እንደሚጭን እና እንደሚሠራ ይገልጻል።
    በጣራው ላይ ወይም እራስን የያዙ ዩኒት ተቆጣጣሪዎች ላይ የቴክኒክ ድጋፍ ለማግኘት የዳይኪን አፕላይድ የአየር ቴክኒካል ምላሽ ማዕከልን በ 800-432-1342 (AAHTechSupport@daikinapplied.com).
  • የቺለር አሃድ ተቆጣጣሪ ድጋፍ ለማግኘት ዳይኪን አፕላይድ ቺለር ቴክኒካል ምላሽ ማዕከልን በ ላይ ያግኙ 800-432-1342 (CHLTechSupport@daikinapplied.com).
    For technical support on PreciseLine unit controllers, contact the Daikin Applied Air Technical Response Center at 800-432-3928 (ATSTechSupport@daikinapplied.com)

የምርት መረጃ

  • የርቀት ተጠቃሚ በይነገጽ ለእይታ፣ ለስርዓት ውቅር፣ ለማዋቀር እና ለማይክሮቴክ ዩኒት ተቆጣጣሪዎች የተነደፈ ነው፡-

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (1)

  • ከዩኒት-ሊሰካው የመቆጣጠሪያ ቁልፍ ሰሌዳ/ማሳያ በተጨማሪ፣ የማይክሮቴክ ዩኒት መቆጣጠሪያ ሲስተሞች በአንድ በይነገጽ እስከ ስምንት አሃዶችን የሚያስተናግድ የርቀት ተጠቃሚ በይነገጽ ሊገጠሙ ይችላሉ። የርቀት ተጠቃሚ በይነገጽ ከዩኒት-ሊሰካው መቆጣጠሪያ ጋር ተመሳሳይ የሆኑ የክፍል ምርመራዎችን እና የቁጥጥር ማስተካከያዎችን ያቀርባል።

ባህሪያት

  • Push-and-roll navigation wheel with an 8-line by 30- character display format
  • Operating conditions, system alarms, control parameters and schedules are monitored
  • RS-485 or KNX interface for local or remote installation
  • Power from controller, no additional power supply necessary
  • Supports panel mounting and wall mounting

አደገኛ የመረጃ መልዕክቶችአደጋ

  • አደጋ አደገኛ ሁኔታን ያመለክታል, ይህም ካልተወገዱ ሞት ወይም ከባድ ጉዳት ያስከትላል.
  • የማስጠንቀቂያ ማስጠንቀቂያ አደገኛ ሊሆኑ የሚችሉ ሁኔታዎችን ይጠቁማል፣ ይህም ካልተወገዱ በንብረት ላይ ጉዳት፣ በግል ጉዳት ወይም ሞት ሊያስከትሉ ይችላሉ።
  • ይጠንቀቁ ጥንቃቄ አደገኛ ሊሆኑ የሚችሉ ሁኔታዎችን ያሳያል፣ ይህም ካልተወገዱ ቀላል ጉዳት ወይም የመሳሪያ ጉዳት ሊያስከትል ይችላል።
  • ማስታወቂያ ማሳሰቢያ ከአካላዊ ጉዳት ጋር ያልተያያዙ ልምዶችን ያመለክታል።

የማጣቀሻ ሰነዶች

ቁጥር ኩባንያ ርዕስ ምንጭ
 

አይኦኤም 1202

 

ዳይኪን ተተግብሯል

ፓዝፋይንደር ቺለር ሞዴል AWS ጭነት፣ አሠራር እና የጥገና መመሪያ  

 

 

 

 

 

 

 

 

 

 

www.ዳይኪን ተተግብሯል.ኮም

 

አይኦኤም 1206

 

ዳይኪን ተተግብሯል

Trailblazer Chiller ሞዴል AGZ ጭነት ፣የሥራ እና የጥገና መመሪያ
 

አይኦኤም 1242

 

ዳይኪን ተተግብሯል

ፓዝፋይንደር ሞዴል AWV Chiller ተከላ፣ ኦፕሬሽን እና የጥገና መመሪያ
 

አይኦኤም 1033

 

ዳይኪን ተተግብሯል

ትልቅ ሞዴል WME፣ B vintagሠ መግነጢሳዊ ቤርንግ ሴንትሪፉጋል ቺለር ተከላ፣ ኦፕሬሽን እና የጥገና መመሪያ
 

አይኦኤም 1264

 

ዳይኪን ተተግብሯል

የአሳሽ ሞዴል WWV/TWV በውሃ የቀዘቀዘ ቺለር ተከላ፣ ኦፕሬሽን እና የጥገና መመሪያ
አይኦኤም 1243 ዳይኪን ተተግብሯል Trailblazer Chiller ሞዴል AMZ
 

ኦኤም 1382

 

ዳይኪን ተተግብሯል

Rebel Commercial የታሸገ የጣሪያ ስርዓት፣ ኦፕሬሽን እና የጥገና መመሪያ
 

ኦኤም 1373

 

ዳይኪን ተተግብሯል

Rebel Applied Rooftop Systems፣ኦፕሬሽን እና የጥገና መመሪያ
 

ኦኤም 1357

 

ዳይኪን ተተግብሯል

የትክክለኛ መስመር አየር ተቆጣጣሪ ፣ ኦፕሬሽን እና የጥገና መመሪያ

የአካላት ውሂብ

አጠቃላይ

  • ምስል 1 የርቀት የተጠቃሚ በይነገጽ የሃርድዌር ንድፍ ዝርዝሮችን ያሳያል።

አጠቃላይ የአካል አቀማመጥ የሚከተሉትን ያጠቃልላል ።

  • 5.7 × 3.8 × 1 in (144 × 96 × 26 mm) size
  • 9.1 oz (256.7 g) weight, excluding packaging
  • የፕላስቲክ መኖሪያ ቤት

ኃይል

  • Supplied by the MicroTech unit controller for direct connection
  • Separate 24V DAC power supply, optional for daisy chain connections, Max 85 mA
  • ማሳሰቢያ፡ የዳይኪን አፕላይድ የአየር ቴክኒካል ምላሽ ማእከልን በ ላይ ያግኙ 800-432-1342 (AAHTechSupport@daikinapplied.com) ወይም የቺለር ቴክኒካል ምላሽ ማዕከል በ 800-432-1342 (CHLTechSupport@daikinapplied.com) የተለየ የኃይል አቅርቦት ከተፈለገ።

ማሳያ

  • LCD type FSTN
  • Resolution dot-matrix 96 x 208
  • Backlight blue or white, user selectable

የአካባቢ ሁኔታዎች

  • Operation EC 721-3-3
  • Temperature -40…158°F (-40…+70°C)
  • Restriction LCD -4…140°F (-20…+60°C)
  • Restriction Process-Bus -13…158°F (-25….+70°C)
  • Humidity < 90% RH (no condensation)
  • Air pressure Min. 10.2 psi (700 hPa), corresponding to max. 9843 ft (3000 m) above sea level

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (2)

መጫን

  • ቅድመ-መጫን
  • የርቀት ተጠቃሚ በይነገጽን ከመጫንዎ እና ከመጫንዎ በፊት እባክዎ የሚከተሉትን ይጠንቀቁ።

የአካባቢ ግምት

  • ትክክለኛውን አሠራር ለማረጋገጥ የርቀት የተጠቃሚ በይነገጽ አቀማመጥ አስፈላጊ ነው. ቦታን በሚመርጡበት ጊዜ የሚከተሉትን ያስወግዱ:
  • Locations that are outside the operating temperature and humidity range (see Environmental Conditions.)
  • Mounting on rooftop without a careful site evaluation and confirmation
  • Walls that are subject to high vibration
  •  Areas with high humidity exterior walls and other walls that have a temperature differential between the two sides
  • Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys, or other heat-generating equipment.

የመጫኛ ወለሎች

  • ላዩን ለመጫን የርቀት ተጠቃሚን በይነገጽ እንደ ሉህ ሮክ ወይም ፕላስተር፣ የቁጥጥር ፓነል ወይም የኤሌክትሪክ መጋጠሚያ ሳጥን ወደ ጠፍጣፋ ወለል ላይ ይስቀሉ።
  • If mounting onto sheet rock or plaster, use anchors, if necessary
  • For mounting in the unit controller panel, electrical junction box, or other metal enclosure, use the supplied magnets.

ክፍሎች

መግለጫ ክፍል ቁጥር
የማይክሮቴክ የርቀት ተጠቃሚ በይነገጽ 1934080031,2
Connectors (using CE+ CE- connection option) 193410302
  1. Note that part number 193408001 is no longer available.
  2. For daisy-chaining unit controllers together, a 2-pin connector (PN 193410302), is required for each unit controller. The 2-pin connector is not required for direct-connecting unit controllers.
  3. የአካባቢዎትን ክፍሎች ቢሮ ለማግኘት፣ ይጎብኙ www.DaikinApplied.com ወይም 800-37PARTS ይደውሉ (800-377-2787).
  4. መጫን እና ማገናኘት
  5. የሚከተለው ክፍል የርቀት ተጠቃሚ በይነገጽ እንዴት እንደሚሰቀል እና ከአንድ ወይም ከዛ በላይ የማይክሮ ቴክ ዩኒት መቆጣጠሪያዎች ጋር እንደሚያገናኘው ይገልጻል።
  6. Electrostatic discharge hazard. Can cause equipment damage. This equipment contains sensitive electronic components that may be damaged by electrostatic discharge from your hands. Before you handle a communication module, you need to touch a grounded object, such as the metal enclosure, in order to discharge the electrostatic potential from your body.
  7. WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded.

Only personnel knowledgeable in the operation of the equipment being controlled must perform connections and service to the unit controller.

  1.  Remove plastic cover (Figure 2).
  2. Mount the remote user interface. The remote user interface can be either panel-mounted or wall-mounted as shown in Figure 3. See Figure 4 and Figure 5 for terminal connections for each of the mounting locations.

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (3)

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (4)

የርቀት ተጠቃሚን በይነገጽ መዘርጋት

  1. የርቀት ተጠቃሚ በይነገጽን ወደ ማይክሮቴክ ዩኒት መቆጣጠሪያ ማገናኘት በሁለት የተለያዩ መንገዶች ሊከናወን ይችላል።
  2. 1. ዴዚ-ሰንሰለት ግንኙነት እስከ ስምንት ክፍሎች ድረስ።
  3. 2. Direct connection to a single unit controller. Connection and wiring instructions in each case are described in the following section. See Table 1 for wire sizing and distance limitations.
  4. NOTE: Power is supplied by the MicroTech unit controller. If a separate 24V power supply is desired, please contact either the Daikin Applied Air Technical Response Center at (800) 432- 1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical
  5. Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com).

Daisy-Chain Connection Establish a physical connection from the remote user interface to the MicroTech unit controller.

  1.  Connect a twisted pair wire to the CE + and CE – pins of each unit controller and remote user interface (see Figure 4 and Figure 5).
  2. Daisy-chain up to eight MicroTech unit controllers to a single remote user interface. See Figure 5 for wiring details. Note the wire size and distance limitations provided in Table 1.
  3. Cycle power to each MicroTech unit controller once the wiring of the remote user interface is complete.
    NOTE: Downloading and communication using the daisy chain connection may be slower than for the RJ45 (Ethernet) direct connection.

Table 1: Wiring Specifications

የአውቶቡስ ግንኙነት CE+, CE-, not interchangeable
ተርሚናል 2-screw connector
ከፍተኛ. ርዝመት 1000 ጫማ (305 ሜትር)
የኬብል አይነት
Wiring distance up to 500 ft Twisted pair, shielded cable 16 AWG
Wiring distance between 500 – 1000 ft Twisted pair, shielded cable 14 AWG
ከ 1000 ጫማ በላይ የሽቦ ርቀት Not currently supported. Contact the appropriate Daikin Applied Technical Response Center for assistance.

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (5)

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (6)

ቀጥተኛ ግንኙነት

  1. የርቀት ተጠቃሚ በይነገጽ በቀጥታ ወደ አንድ የማይክሮቴክ ዩኒት መቆጣጠሪያ በመደበኛ RJ45 (ኢተርኔት) ግንኙነት ሊገናኝ ይችላል።

አሰራር

  1. Locate the connector location as shown in Figure 6
  2. Follow Figure 6 for connection details. Note the distance limitations provided.
  3. Cycle power to the unit(s) once the wiring of the remote user interface is complete.
  4. ማሳሰቢያ፡ ሃይል የሚቀርበው በዩኒት ተቆጣጣሪ ነው። የተለየ የ24V ሃይል አቅርቦት ከፈለጉ እባክዎን የዳይኪን አፕላይድ የአየር ቴክኒካል ምላሽ ማእከልን በ 800-432-1342 (AAHTechSupport@daikinapplied.com) ወይም የቺለር ቴክኒካል ምላሽ ማዕከል በ 800-432-1342 (CHLTechSupport@daikinapplied.com).

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (7)

ኦፕሬሽን

  • የርቀት ተጠቃሚ በይነገጽን በመጠቀም

የሃርድዌር ባህሪዎች

  • የርቀት የተጠቃሚ በይነገጽ ቁልፍ ሰሌዳ/ማሳያ ባለ 8-መስመር በ 30 ቁምፊ ማሳያ፣ “ግፋ እና ጥቅል” የማውጫጫ ጎማ እና ሶስት አዝራሮች፡ ማንቂያ፣ ሜኑ እና ተመለስ (ስእል 7) ያካትታል።
  • Turn the navigation wheel clockwise (right) or counterclockwise (left) to navigate between lines on a screen and also to increase and decrease changeable values when editing. Press down on the wheel to use it as an Enter button.
  • Press the Back button to display the previous page.
  • Press the Home button to return to the main screen from the current page.
  • Press the Alarm button to view የማንቂያ ዝርዝሮች ምናሌ።

የቁልፍ ሰሌዳ/ማሳያ ባህሪዎች

  • The first line on each page includes the page title and the line number to which the cursor is currently “pointing.” The line numbers are X/Y to indicate line number X of a total of Y lines for that page. The left most position of the title line includes an “up” arrow to indicate there are pages “above” the currently displayed items, a “down” arrow to indicate there are pages “below” the currently displayed items or an “up/down” arrow to indicate there are pages “above and below” the currently displayed page. Each line on a page can contain status-only information or include changeable data fields. When a line contains status-only information and the cursor is on that line, all but the value field of that line is highlighted meaning the text is white with a black box around it. When the line contains a changeable value and the cursor is at that line, the entire line is highlighted.
  • በገጹ ላይ ያለው እያንዳንዱ መስመር እንደ “ዝለል” መስመር ሊገለጽ ይችላል፣ ይህም ማለት የማውጫውን ጎማ መግፋት ወደ አዲስ ገጽ “ዝለል” ያስከትላል። አንድ ቀስት በመስመሩ በስተቀኝ በኩል የ "ዝላይ" መስመር መሆኑን ያሳያል እና ጠቋሚው በዚያ መስመር ላይ በሚሆንበት ጊዜ ሙሉው መስመር ይደምቃል.
  • ማሳሰቢያ፡- ለልዩ አሃድ ውቅር ተፈጻሚ የሚሆኑ ምናሌዎች እና እቃዎች ብቻ ናቸው የሚታዩት።

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (8)

ማንቂያዎች
The Alarm Details Menu includes active alarm and alarm
log information. See Figure 8 for an exampየነቃ ማንቂያ። እንዲሁም ለሚኖሩ የማንቂያ አማራጮች ተገቢውን የማይክሮቴክ ዩኒት ተቆጣጣሪ ኦፕሬሽን ማንዋልን (www.DaikinApplied.com) ይመልከቱ።

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (9)

የይለፍ ቃሎች
የዩኒት ተቆጣጣሪ ምናሌ ተግባራት የተለያዩ የተደራሽነት ደረጃዎች አሏቸው። ችሎታ view እና/ወይም ቅንብሮችን መቀየር በተጠቃሚው የመዳረሻ ደረጃ እና በገባው የይለፍ ቃል ይወሰናል። የይለፍ ቃል መዳረሻ አራት ደረጃዎች አሉ፡-

  1. 1. የይለፍ ቃል የለም.
    2. ደረጃ 2. ከፍተኛው የመዳረሻ ደረጃ. የይለፍ ቃል ሳያስገቡ ተጠቃሚው የመሠረታዊ ሁኔታ ምናሌ ንጥሎችን ብቻ ነው መዳረሻ ያለው። የደረጃ 2 ይለፍ ቃል (6363) ማስገባት ልክ እንደ ደረጃ 4 ከዩኒት ውቅር ሜኑ ጋር ተመሳሳይ መዳረሻ ይፈቅዳል።
    3. ደረጃ 4. የደረጃ 4 የይለፍ ቃል (2526) ማስገባት ልክ እንደ ደረጃ 6 ከኮሚሽኑ ዩኒት ሜኑ፣ ማንዋል ቁጥጥር እና የአገልግሎት ሜኑ ቡድኖች ጋር ተመሳሳይ መዳረሻ ይፈቅዳል።
    4. ደረጃ 6. የደረጃ 6 ይለፍ ቃል (5321) ማስገባት የማንቂያ ዝርዝሮች ሜኑ፣ ፈጣን ሜኑ እና View/የአሃድ ምናሌዎች ቡድን አዘጋጅ።
  2. Alarms can be acknowledged without entering a
    የይለፍ ቃል።
    የይለፍ ቃል ገጹን መድረስ
    The main password page is displayed when the remote user
    interface display (HMI) is first accessed.
    1. የመነሻ አዝራሩን ይጫኑ.
    2. Press the Back button multiple times, or if the keypad/
    display has been idle longer than the Password Timeout
    (default 10 minutes).
    The main password page provides access to enter a
    password, access the Quick Menu, view the current Unit
    State, access the alarm lists or view ስለ መረጃ
    unit (Figure 9).

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (10)

  • የማይክሮ ቴክ ዩኒት ተቆጣጣሪ ኦፕሬሽን ማንዋል (www.DaikinApplied.com) የይለፍ ቃሎችን ለመድረስ እና ለማሻሻል የአሰሳ እና የአርትዖት ሁነታን እንዴት መጠቀም እንደሚቻል ጨምሮ ስለ የይለፍ ቃላት ተጨማሪ መረጃ ይሰጣል።

ማዋቀር

  • The following section describes how to set up the HMI so that it can be used to display, configure, or change unit parameters.
  • Refer to the applicable MicroTech unit controller Operation
  • Manual for a detailed description of chiller or rooftop sequence of operation and keypad menu structure when configuring the unit via the remote user interface (www.DaikinApplied.com).
  • ማሳሰቢያ፡ በዩኒቶች መካከል ለመቀያየር፣ ወደ ዋናው ስክሪን ለመመለስ ለአምስት ሰከንድ የተመለስ ቁልፍን ተጫን።

የተጠቃሚ ምርጫዎችን አብጅ

  1.  Turn power on to the unit controller(s). Power to the remote user interface is provided automatically from the MicroTech unit controller(s) through the RJ45 (Ethernet) direct connection.
  2.  The main screen with HMI Settings and Controller List appears (Figure 10). Use the HMI Settings screen to change options for backlight color, backlight turn off time, contrast, and brightness.
  3. ማሳሰቢያ፡ የመነሻ ቁልፍን ለአምስት ሰከንድ በመጫን ዋናውን ስክሪን በማንኛውም ጊዜ ማግኘት ይቻላል።
  4. Press the navigation wheel to select the HMI Settings menu, if desired.

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (11)

ከማይክሮቴክ ዩኒት መቆጣጠሪያ ጋር ያመሳስሉ።

1. የመቆጣጠሪያ ዝርዝር ስክሪን ለመምረጥ የአሰሳውን ጎማ ይጫኑ (ስእል 11).

  • The Controller List automatically updates each time the remote user interface is powered up so that information is synchronized from the main unit controller.
  • The Controller List screen displays the unit controller(s) connected to the remote user interface. This screen allows the user to select between units, if more than one unit is connected to the remote user interface

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (12)

ማሳሰቢያ፡- አንድ ነጠላ ዩኒት ከርቀት የተጠቃሚ በይነገጽ ጋር ከተገናኘ እንደ ምርጫ አማራጭ በስክሪኑ ላይ ይታያል።

  • Turn the navigation wheel clockwise and then press down to select the desired unit.
  • The Information screen appears as the remote user interface performs a download sequence to import the necessary information from the main unit controller. A status bar appears on the Downloading the Objects screen to indicate that the download is in process (Figure 12).
  • ማሳሰቢያ፡ የርቀት ተጠቃሚ በይነገጹ በመነሻ ማውረጃ ቅደም ተከተል ላይ “የቀዘቀዘ” መስሎ ከታየ የመላ መፈለጊያውን ክፍል ይመልከቱ።

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (13)

  1. Once the first unit has been downloaded, select the next unit controller, if applicable. The download process is required for each unit controller connected to the remote user interface.
  2.  Press the Home button for five seconds to return to the main screen.
  3. NOTE: The Downloading the Objects sequence generally takes a minute or less when direct-connecting to a single unit. However, the downloading sequence takes longer when using the daisy-chain connection. When the download sequence is complete, the
  4. Main screen of the unit controller appears on the remote user interface. At this point, the remote user interface and unit controller are synchronized.
  5.  Access and adjust the same parameters that are available via the unit controller keypad/display. Refer to the applicable MicroTech unit controller Operation Manual for the keypad menu structure and detailed description the unit controller sequence of operation (www.DaikinApplied.com).

የጽኑዌር ማሻሻያ ሂደት

  1. የርቀት የተጠቃሚ በይነገጽ (HMI) firmware (.bin) ለማዘመን እነዚህን ደረጃዎች ይከተሉ። file.
  2. NOTE: The upgrade procedure requires the use of an SD memory card no larger than 8GB with a FAT32 file የስርዓት ቅርጸት.
  3. ማሳሰቢያ፡- v1.07 firmware ባላቸው አሃዶች የመስክ ማሻሻያ ማድረግ አይቻልም። የዳይኪን አፕላይድ የአየር ቴክኒካል ምላሽ ማዕከልን በ ላይ ያግኙ 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at (800) 432- 1342 (CHLTechSupport@daikinapplied.com) ለእርዳታ ፡፡

መላ መፈለግ

  1. ይህ ክፍል አጋዥ መረጃዎችን፣ ተደጋግመው የሚጠየቁ ጥያቄዎችን እና ሌሎች ከሩቅ የተጠቃሚ በይነገጽ ጋር የተያያዙ ጠቃሚ ምክሮችን ይዟል።

ሠንጠረዥ 2 - የመላ ፍለጋ መመሪያ

ችግር መፍትሄ
 

 

During the initial download sequence, the keypad/display appears to

freeze up and a “Loading….. Lost

Connection” message appears.

The remote user interface is stuck in the downloading sequence due to incompatibility with v1.07 application software. The remote user interface must be updated to v10.22 or newer application software. Contact Daikin Applied Air Technical Response

at 800-432-1342 ለተጨማሪ መመሪያዎች.

 

The remote user interface has been connected to the

MicroTech unit controller but the display remains blank after power-up.

 

Verify that the unit controller has power. Check wiring from

the unit controller to the remote user interface. Note that inputs and outputs are polarity-sensitive.

የርቀት ተጠቃሚ በይነገጽ የግንኙነት መጥፋት እያጋጠመው ነው። The site may have “dirty power” or electrical noise causing loss of

communication. See below for further instruction.

  1. Access the Power Bus menu on the MicroTech unit controller by the following keypad menu path: service menu/HMI setup/PBusPwrSply=ON (default). See Figure 13.
  2.  Set the default Power Bus supply.
  3. For the first and last units on the daisy-chain trunk, leave the Power Bus supply at the default of ON.
  4. For all other units within the daisy chain trunk, set the Power Bus supply to the OFF position.

DAIKIN-1005-7-Micro-Tech-Unit-Controller-Remote-FIG- (14)

ጠቃሚ ምክሮች
የአገልግሎት ቴክኒሻኖች ብዙውን ጊዜ ከአንድ ዩኒት መቆጣጠሪያ ጋር የተገናኙ ሁለት የቁልፍ ሰሌዳዎች / ማሳያዎች እንዲኖራቸው ያደርጋቸዋል። የተከፈለ ማያ ማዋቀርን መጠቀም ያስችላል view multiple menu items at the same time during start-up and also for diagnostic purposes. → Simply hook up the first remote user interface with an RJ45 direct connection, and then use a two-wire twisted  pair cable to connect to the second keypad/display.

የክለሳ ታሪክ

ክለሳ ቀን ለውጦች
አይኤም 1005 ጥር 2010 የመጀመሪያ ልቀት
IM 1005-1 ሴፕቴምበር 2010 Added Daikin Trailblazer® chiller model AGZ-D
IM 1005-2 ማርች 2012 Added Rebel® packaged rooftop model DPS. Updated Figure 3 with labels and connector cables.
IM 1005-3 ህዳር 2016 Added models AWV Pathfinder® chiller and AGZ-E Trailblazer® chiller, added RJ45 direct connection option, corrected bus wiring distance limitations, Troubleshooting section, Daikin branding and formatting updates
IM 1005-4 ጥር 2018 WME እና WWV ማቀዝቀዣ ሞዴሎች ታክለዋል።
IM 1005-5 ኦገስት 2019 Updated connections
IM 1005-6 ሰኔ 2023 የምርት ስም እና ሌሎች የቅርጸት ዝመናዎች።
IM 1005-7 ጁላይ 2025 Updated contact information, added Daikin Trailblazer® chiller model AMZ, and removed model lists from front cover.

 

ዳይኪን ተግባራዊ ስልጠና እና ልማት
Now that you have invested in modern, efficient Daikin Applied equipment, its care should be a high priority. For training information on all Daikin Applied HVAC products, please visit us at www. DaikinApplied.com and click on Training, or call 540-248-9646 እና የስልጠና መምሪያውን ይጠይቁ.

ዋስትና
ሁሉም የዳይኪን አፕሊይድ መሳሪያዎች የተገደበ የምርት ዋስትናን ጨምሮ በመደበኛ የሽያጭ ውል እና የሽያጭ ሁኔታዎች ይሸጣሉ። የዋስትና ዝርዝሮችን ለማግኘት የአካባቢዎን የዳይኪን አፕላይድ ተወካይ ያማክሩ። የአካባቢዎን ዳይኪን አፕላይድ ተወካይ ለማግኘት ወደ www.DaikinApplied.com ይሂዱ።

ከገበያ በኋላ አገልግሎቶች
የአካባቢዎትን ክፍሎች ቢሮ ለማግኘት፣ www.DaikinApplied.comን ይጎብኙ ወይም ወደ 800-37PARTS ይደውሉ (800-377-2787). የአካባቢዎን የአገልግሎት ቢሮ ለማግኘት፣ ይጎብኙ www.DaikinApplied.com ወይም ይደውሉ 800-432-1342. ይህ ሰነድ በዚህ ህትመት ውስጥ በጣም ወቅታዊውን የምርት መረጃ ይዟል። በጣም ወቅታዊውን የምርት መረጃ ለማግኘት እባክዎ ወደ ይሂዱ www.DaikinApplied.com.Products manufactured in an ISO Certified Facility.

የሚጠየቁ ጥያቄዎች

ጥ፡ የርቀት ተጠቃሚ በይነገጽ ስንት አሃዶችን ማስተናገድ ይችላል?

A: The remote user interface can handle up to eight units per interface.

Is a separate 24V power supply necessary for direct connection?

አይ፣ ሃይል የሚሰጠው በማይክሮቴክ ዩኒት ተቆጣጣሪ ነው።

What type of cable is recommended for daisy-chain connection?

ዳይኪን አፕሊይድ በአጠቃላይ የተጠማዘዘ ጥንድን፣ 16 AWG የተከለለ ገመድ እስከ 500 ጫማ እና 14 AWG ከ500 እስከ 1000 ጫማ እንዲጠቀሙ ይመክራል። ረጅም ርቀት ለሚፈልጉ አፕሊኬሽኖች ተገቢውን የቴክኒክ ምላሽ ማዕከል ያግኙ።

የርቀት ተጠቃሚ በይነገጽ (HMI) firmware ማሻሻል እንዳለብኝ ወይም መቼ እንደሚያስፈልገኝ እንዴት አውቃለሁ files?

If the remote user interface seems to freeze during initial download process If wiring has been confirmed (inputs and outputs are polarity sensitive) and HMI is not responding See Firmware Upgrade Procedure section for details.

የማይክሮቴክ ዩኒት መቆጣጠሪያ firmwareን ማሻሻል ብፈልግስ?
የዳይኪን አፕላይድ የአየር ቴክኒካል ምላሽ ማእከልን በ ላይ ያግኙ 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com) ለእርዳታ ፡፡