WEINTEK MODBUS HMI RTU Controller

WEINTEK-MODBUS-HMI-RTU-Controller-PRODUCT

የምርት ዝርዝሮች

  • Supported Series: MODBUS RTU CONTROLLER
  • Communication Protocols: MODBUS RTU, RTU over TCP
  • PLC Connection Interfaces: RS485, RS232/RS485/USB
  • Baud Rate: 9600 (Configurable range: 9600~115200)
  • የውሂብ ቢት: 8
  • Parity Options: Even, Odd, None
  • Stop Bits: 1 (Configurable: 1, 2)
  • PLC Station Number Range: 0-255

የምርት አጠቃቀም መመሪያዎች

HMI ቅንብር፡
የHMI ቅንብሮችን እንደሚከተለው ያዋቅሩ።

  • PLC Type: MODBUS RTU, RTU over TCP
  • PLC Interface: RS-485
  • የባውድ መጠን: 9600
  • የውሂብ ቢት: 8
  • Parity: Even (Other options: Odd, None)
  • Stop Bits: 1 (Other option: 2)
  • PLC Station Number Range: 0-255

የ PLC ቅንብር፡-
Set up the PLC communication mode and device address as follows:

  • Communication Mode: Modbus RTU Protocol
  • Device Address Configuration based on Bit/Word Device Types

ማስታወሻ፡- Refer to the user manual for specific configurations related to device types and address ranges.

MODBUS RTU, RTU over TCP
Supported Series: MODBUS RTU CONTROLLER Webጣቢያ፡ http://www.modbus.org

HMI ቅንብር፡

መለኪያዎች የሚመከር አማራጮች ማስታወሻዎች
PLC አይነት MODBUS RTU, RTU over TCP  
PLC I/F RS485 RS232/RS485/USB  
የባውድ መጠን 9600 9600~115200  
የውሂብ ቢት 8 8  
እኩልነት እንኳን እንኳን ፣ ጎዶሎ ፣ ምንም  
ቢትስ አቁም 1 1፣ 2  
PLC sta. No. 1 0-255  
የመስመር ላይ አስመሳይ አዎ የስርጭት ትዕዛዝ አዎ
Extend the address mode አዎ    

WEINTEK-MODBUS-HMI-RTU-Controller-FIG- (1)

Address Range Limit
The address range for device types 0x, 1x, and 0x_multi_coils can be configured. This option should be used when the controller’s bit register address range is not a multiple of 16. For example, if the range is 0x1 ~ 0x6 or 0x9 ~ 0x14, communication will not be possible. To ensure effective communication between the HMI and the controller, please follow the configuration instructions below.
0x-1~6

WEINTEK-MODBUS-HMI-RTU-Controller-FIG- (2)

0x_1-9~14

WEINTEK-MODBUS-HMI-RTU-Controller-FIG- (3)

ልወጣ
The 3x_Double and 4x_Double address types are added. If [ABCD ->CDAB] check box is selected, please select 3x_Double and 4x_Double address types.

የ PLC ቅንብር

የግንኙነት ሁነታ Modbus RTU ፕሮቶኮል

የመሣሪያ አድራሻ

ቢት/ቃል የመሳሪያ ዓይነት ቅርጸት ክልል ማስታወሻ
B 0x ዲዲዲዲ 1 ~ 65535 Output bit
B 0x_multi_coils ዲዲዲዲ 1 ~ 65535 ብዙ ጥቅልሎችን ይፃፉ
B 0x_single_bit ዲዲዲዲ 1 ~ 65535 * ማስታወሻ 4
B 1x ዲዲዲዲ 1 ~ 65535 Input bit (read only)
B 1x_single_bit ዲዲዲዲ 1 ~ 65535 * ማስታወሻ 4
B 3x_Bit DDDDDdd 100 ~ 6553515 Input Register bit (read
B 4x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 6x_Bit DDDDDdd 100 ~ 6553515 Output Register bit
B 0x_1 ዲዲዲዲ 1 ~ 65535  
B 0x_2 ዲዲዲዲ 1 ~ 65535  
B 0x_3 ዲዲዲዲ 1 ~ 65535  
B 0x_4 ዲዲዲዲ 1 ~ 65535  
B 0x_5 ዲዲዲዲ 1 ~ 65535  
B 0x_6 ዲዲዲዲ 1 ~ 65535  
B 0x_7 ዲዲዲዲ 1 ~ 65535  
B 0x_8 ዲዲዲዲ 1 ~ 65535  
B 0x_9 ዲዲዲዲ 1 ~ 65535  
B 1x_1 ዲዲዲዲ 1 ~ 65535  
B 1x_2 ዲዲዲዲ 1 ~ 65535  
B 1x_3 ዲዲዲዲ 1 ~ 65535  
B 1x_4 ዲዲዲዲ 1 ~ 65535  
B 1x_5 ዲዲዲዲ 1 ~ 65535  
B 1x_6 ዲዲዲዲ 1 ~ 65535  
B 1x_7 ዲዲዲዲ 1 ~ 65535  
B 1x_8 ዲዲዲዲ 1 ~ 65535  
B 1x_9 ዲዲዲዲ 1 ~ 65535  
W 3x ዲዲዲዲ 1 ~ 65535 Input Register (read only)
W 3x_MAX1W ዲዲዲዲ 1 ~ 65535 Display 32 bits *Note1
DW 3x_MAX2W ዲዲዲዲ 1 ~ 65535 * ማስታወሻ 1
W 3x_Double ዲዲዲዲ 1 ~ 65535 * ማስታወሻ 2
QW 3x_QWord ዲዲዲዲ 1 ~ 65535 64-ቢት
W 4x ዲዲዲዲ 1 ~ 65535 Output Register
W 4x_MAX1W ዲዲዲዲ 1 ~ 65535 Display 32 bits *Note1
DW 4x_MAX2W ዲዲዲዲ 1 ~ 65535 * ማስታወሻ 1
W 4x_Double ዲዲዲዲ 1 ~ 65535 * ማስታወሻ 2
ቢት/ቃል የመሳሪያ ዓይነት ቅርጸት ክልል ማስታወሻ
W 4x_32Bit ዲዲዲዲ 1 ~ 65535 Output Register *Note 1
QW 4x_QWord ዲዲዲዲ 1 ~ 65535 64-ቢት
W 0x_single_coil ዲዲዲዲ 1 ~ 65535 * ማስታወሻ 3
DW 5x ዲዲዲዲ 1 ~ 65535 4x double word swap
W 6x ዲዲዲዲ 1 ~ 65535 4x single word writeማስታወሻ 1

1: MAX1W and 4X_32Bit read/write 1 word for each packet and display a 32-bit value, whereas MAX2W reads/writes 2 words for each packet.

ማስታወሻ2: Go the [System Parameter Settings] -> [Device Properties] and click [Conversion] to set the data format of device types 3x, 4x, 6x, 3x_double, 4x double.

WEINTEK-MODBUS-HMI-RTU-Controller-FIG- (5)

ማስታወሻ3፡ Read/write a Bit at a time. Value 0 and 1 are used to represent ON or OFF status where 0 means set OFF and 1 means set ON.

ማስታወሻ4፡ The number of bits to read can be set in Macro; therefore, it is recommended to use 0x address type for functions such as GetData() and SetData(), in order to increase reading speed.
To read/write multiple 0x address tytypesn ma acro, use 0x_multi_coils to increase write speed.

ማስታወሻ5፡ Please assign all the addresses to Even addresses, or all to Odd addresses, in order to prevent communication failure.

ማስታወሻ 6፡- EBPro V6.03.02 or later supports 64-bit data type (cMT Series only), but please note that the address limit range is 48 bits in maximum..

ማስታወሻ፡-
Address type “5x” is mapped to Holding Register. The communication protocol of 5x is almost the same as “4x” except that “5x” swaps double word.
If 4x contains the following information:

አድራሻ 1 2 3 4 5 6
Data in word 0x1 0x2 0x3 0x4 0x5 0x6  
ውሂብ 0x0201 0x0403 0x0605  

For 5x, it will be:

አድራሻ 1 2 3 4 5 6
Data in word 0x1 0x2 0x3 0x4 0x5 0x6  
ውሂብ 0x0102 0x0304 0x0506  

Modbus RTU function code:

የመሳሪያ ዓይነት አንብብ ጻፍ
0x 0x01 Read coil 0x05 Write single coil
0x_multi_coils 0x01 Read coil 0x0f write multiple coils
1x 0x02 Read discrete input X
3x / 3x_Bit 0x04 Read input register X
4x / 4x_Bit 0x03 Read holding register 0x10 Write multiple registers
5x 0x03 Read holding register 0x10 Write multiple registers
6x 0x03 Read holding register 0x06 Write a single register
0x_single_coil 0x01 Read coil 0x05 Write single coil

ሽቦ ዲያግራም

ንድፍ 1

RS-232
The serial port pin assignments may vary between HMI models. Please click the following link for more information.

WEINTEK-MODBUS-HMI-RTU-Controller-FIG- (6)

ንድፍ 2

RS-485 4 ዋ
The serial port pin assignments may vary between HMI models. Please click the following link for more information.

WEINTEK-MODBUS-HMI-RTU-Controller-FIG- (7)

ንድፍ 3

RS-485 2 ዋ
The serial port pin assignments may vary between HMI models. Please click the following link for more information.

WEINTEK-MODBUS-HMI-RTU-Controller-FIG- (8)

በተደጋጋሚ የሚጠየቁ ጥያቄዎች

  • Q: What is the purpose of the conversion in a PLC setting?
    A: The conversion setting is used to manage the data format of specific device types such as 3x, 4x, and others. It allows for proper data interpretation and communication between the HMI and the controller.
  • Q: How does address type 5x differ from address type 4x?
    A: Address type 5x is mapped to Holding Register and swaps double words compared to address type 4x. The communication protocol for both is similar, with the main distinction being the double word swapping in address type 5x.
  • Q: What are the options available for device properties conversion?